Table V Electrical Specications
Parameter Value
Input
Voltage (nominal), VAC
120 or 230, optional 220, optional 210 for FXM 2000, 120 only for FXM 650-48
Frequency, Hz, ±5%
60/50 (auto-detection), Output frequency = Input frequency
Current, Amps 
(@ nominal Vin an d max 
batt ery char ging current)
FXM 650-24: 8.7/4.5 @120/230 VAC
FXM 650-48: 10.5 @120 VAC
FXM 1100: 15.5/8 @120/230 VAC
FXM 2000: 20/12 @120/230 VAC
Input Circuit Breaker 
Ratings, Amps 
FXM 650-24: 15/10 @120/230 VAC
FXM 650-48: 15 @120 VAC
FXM 1100: 20/10 @120/230 VAC
FXM 2000: 25/15 @120/230 VAC
Battery Circuit Breaker 
Ratings, Amps
FXM 650-48/1100: 50
FXM 650-24/2000: 80
Output
Voltage (nominal), VAC
120 or 230, optional 220, optional 210 for FXM 2000, 120 only for FXM 650-48
Frequency, Hz, ±5%
60/50 (output frequency = input frequency.)
Power, W/VA
FXM 650: 650
FXM 1100: 1100
FXM 2000: 2000
Waveform
Pure sine wave
Load Crest Factor
3:1 (load dependent)
Output Voltage Distortion
< 3% THD (resistive load)
Efficiency 
7
Normal Mode
Backup (Inverter) Mode
> 98%
> 82% (48 Vbatt), >75% (24 Vbatt)
Transfer Time, mS 
AVR to Backup
Backup to AVR
5 (typical)
5 (typical)
Line Qualifica tion Time, 
Seconds
3 (factory default), user adjustable to 3, 10, 20, 30, 40, or 50.
Battery String Voltage
FXM 650 - 24: 24 VDC
FXM 650 - 48/1100/2000: 48 VDC
1. Capable of operating at 73% of rated full load for up to 2 hours at 74°C. Above 55°C ambient, derate output power by 1.4% per °C rise,
up to 74°C max.
2. Capable of operating at 100% of rated full load below 0°C down to -40°C after the Alpha FXM has been stabilized at 0°C for at least 1
hour.
3. FXM 1100/2000-120V only: above 50°C ambient, derate output power by 1.1% per °C rise, up to 74°C max.
4. Derate 2°C per 300 m (1000 ft) above 1400 m (4500 ft).
5. For FXM650/1100-48(Q), the default setting of C3 is “FAULT”.
6. The LCD display may not function below -15°C. It gradually resumes normal operation as the temperature rises above -15°C. This will not
affect the operation of the Alpha FXM.
Table U Mechanical Specications
Parameter Value
User inputs
Three optically-isolated and powered inputs are located on the front panel. When
they are shorted, their functions are:
S1: Starts the self test.
S2: Activates an alarm.
S3: Unit shutdown.
User interface
6
2 x 20 backlit alpha-numeric LCD screen. Three control buttons located below.
Page view 79