F R O M A L P H A T E C H N O L O G I E S
Operator’s Manual
U N I N T E R R U P T I B L E P O W E R S U P P L I E S
Alpha CFR 1500 and
CFR 1500RM
USA & LATIN AMERICA
Alpha Technologies
3767 Alpha Way
Bellingham, WA 98226
Tel: (360) 647-2360
Fax: (360) 671-4936
UNITED KINGDOM
Alpha Technologies
Cartel Business Estate
Edinburgh Way
Harlow, Essex CM20 2DU
Tel: +44-1279-422110
Fax: +44-1279-423355
GERMANY
Alpha Technologies
Hansastrasse 8
D-91126 Schwabach
Tel: +49-9122-997303
Fax: +49-9122-997321
MIDDLE EAST
Alphatec
P.O. Box 6468
3307 Limassol, Cyprus
Tel: +357-5-375675
Fax: +357-5-359595
Alpha sales and service offices located throughout the world
http://www.alpha-us.com
Printed in the Canada 017-102-B0-002 3/97
CANADA & ASIA PACIFIC
Alpha Technologies
7033 Antrim Ave.,
Burnaby BC V5J 4M5
Tel: (604) 430-1476
Fax: (604) 430-8908
AUSTRALIA
Alpha Technologies
8 Anella Ave., Unit 6
Castle Hill, NSW 2154
Tel: +61 (0)2 9894-7866
Fax: +61 (0)2 9894-0234
©1997 Alpha Technologies
Page view 0
1 2 3 4 5 6 ... 82 83

Summary of Contents

Page 1 - Operator’s Manual

F R O M A L P H A T E C H N O L O G I E SOperator’s ManualU N I N T E R R U P T I B L E P O W E R S U P P L I E SAlpha CFR 1500 andCFR 150

Page 2 - SAVE THESE INSTRUCTIONS

41.3 Unpacking and InspectionCarefully remove the UPS from its shipping container. Inspect the contents.If items appear to be damaged or missing, con

Page 3 - LIMITED 24-MONTH WARRANTY

52. FEATURES2.1 A Tour of the CFRThe Alpha CFR is designed to be easy to use and extremely flexible. TheCFR’s interchangeable front panel interface d

Page 4

62. FEATURES2.3 CFR Rear Panel1. AC Line CordThe UPS is equipped with a standard, grounded AC line cord.2. EXTERNAL BATTERY ConnectorThe connector ac

Page 5 - Uninteruptible Power Supplies

7Fig. 2aCFR 1500RM Rear Panel2. FEATURESFig. 2bCFR 1500 Rear Panel2.3 CFR Rear Panel10. Exhaust FanThe CFR1500 contains a rear panel exhaust fan to e

Page 6 - 7. SPECIFICATIONS

8LOW BATTE R YWARN INGLO W BATTER YSHUTDOWNLINE PRESENTLINE FAILURESE R VICETESTALPHATECHNOLOGIESALARM OFFOUTPUT LOADOVERLOAD100 %75 %50 %25 %MAN

Page 7

92. FEATURESFig. 4Intelligent Interface Device2.4 Information Management Options, continuedIntelligent Interface Device (optional)The Intelligent Inte

Page 8

102. FEATURES2.5 Communication / Interface OptionsThe CFR is equipped with four rear panel jacks for communication andremote interfaces: RS-232 Serial

Page 9

112. FEATURES2.5 Communication / Interface Options, continuedPin 1 Pin 1RJ-45(External Alarms)MMJ(External IID)Fig. 5CFR-UPS Connector Identification

Page 10 - continued

122. FEATURESLAN Interface ConnectorThe Alpha UPS provides a LAN interface port on a DE-9 female connector.This port may be used to monitor the status

Page 11 - 6.6 Troubleshooting Guide

13External IID ConnectorThe external IID connector provides an interface for the optional desktopIntelligent Interface Device (IID). This allows the

Page 12 - CFR 1500 only

IMPORTANT SAFETY INSTRUCTIONSCONTAINED IN THIS MANUALCAUTION: To reduce the risk of electrical shock, and to ensure the safe opera-tion of this unit,

Page 13

14Fig. 8External Alarms Connector Pin-out(with Factory installed EPO Switch Option)2.5 Communication / Interface Options, continued2. FEATURESPin 1N.C

Page 14

152.6 RS-232 Communication Options2. FEATURESRS–232 ConnectorThe connection/specifications for the RS–232 serial port vary dependingon the installed i

Page 15 - 6.3 Battery Testing

16Terminal Emulation SetupIf you are using a PC with terminal emulation software (such as PROCOMM)to communicate with the CFR, use the following setup

Page 16 - 6.2 Battery Maintenance

172. FEATURES2.6 RS–232 Communication Options, continuedDesktop IID RS–232 PortThe RS–232 port on the desktop IID can be used for access with a PC ora

Page 17

183. INSTALLATION3.1 Pre-InstallationDo not connect the CFR UPS to a line conditioner, isolation transformer orany other similar type of device. Dama

Page 18

193. INSTALLATION3.2 Connecting the CFR (Plug and receptacle)CAUTION: Installation and wiring should be performed by qualified servicepersonnel in ac

Page 19

203. INSTALLATION3.2.1 Terminal Block Input and Output Wiring1. Connect a dedicated ground wire from the GROUND lug on the back of the CFRto an electr

Page 20

213. INSTALLATION3.2.1 Terminal Block Input and Output Wiring, continued* CAUTION: Refer to the nameplate voltage and frequency ratings affixed to the

Page 21

22The CFR is designed so that battery backup time can be greatly extendedsimply by plugging the EBP 48 External Battery Pack to the back of the UPS.Ba

Page 22 - DB-25 Male (DTE)DE-9 Male

23In North America, there are only two recognized supply voltages: 208VAC (most commonly used in industrial, commercial, and office areas); and 240VA

Page 23

THE ALPHA CFRIMPORTANT SAFETY PRECAUTIONSCarefully unpack the unit. Report any shipping damage immediately.Please read the operators manual. If you

Page 24 - 5. TERMINAL COMMUNICATION

243.4 208 VAC vs 240 VAC (60 Hz) ConfigurationsSince loads are shared, it is possible to exceed the rated maximum outputcurrent of one of the transfor

Page 25

253. INSTALLATION3.4 208 VAC vs 240 VAC (60 Hz) ConfigurationsFig.14208 VAC Output Schematic (for reference only)Fig. 15120/120/240 VAC Power distribu

Page 26

264.1 Start-up, Test and ShutdownNOTE: ALL rack mount units require an external battery pack. Beforeattempting to operate these units without a batte

Page 27

27Manual Self-testPress (and hold for several seconds) the “MANUAL START” switch, locatedon the Standard Interface Panel, when the UPS is running on A

Page 28 - - inverter on)

284. OPERATION4.1 Start-up, Test and Shutdown, continuedSwitching OFF the UPS:1. Switch all equipment connected to the UPS OFF.2. Switch the rear pane

Page 29

294.2 External Modem ConfigurationSpecificationsModem: USRobotics Sportster external modem, 1200, 9600, 19.2K, or28.8K baud or any Hayes compatible mo

Page 30

304. OPERATION4.2 External Modem Configuration, continuedEnabling External ModemAll CFRs are shipped with the modem feature disabled. The followingc

Page 31

314.2 External Modem Configuration, continuedConfiguring the modem to work with CFRThe CFR uses a three wire interface (RX, TX, and GND) to communicat

Page 32

324.3 External Modem Operation4. OPERATIONInitializing the ModemFor proper operation, the CFR needs to initialize the modem before usingit. Since a

Page 33 - 5.7 Output Parameters

334.3 External Modem Operation, continued4. OPERATIONSending Automatic Alarms When a power event takes place, the CFR stores it in an event buffer.

Page 34

IMPORTANT SAFETY PRECAUTIONSThe CFR1500 and CFR1500RM Series units contain sealed, Lead-Acid batteriesconsisting of:Four batteries, six cells each, 48

Page 35

344.3 External Modem Operation, continued4. OPERATIONRemote Access Using External ModemWhen the remote access feature is enabled, the CFR sends the a

Page 36 - 5.4 Menu Commands Overview

35LOW BATTERYWARN INGLOW BATTERYSHUTDOWNLINE PRESENTLINE FA I LU RESERVICE TESTALPHATEC HN O LO G IE SALARM OFFOUTPUT LOADOVERLOAD100 %75 %50 %2

Page 37

36LOW BATTERYWARN INGLOW BATTERYSHUTDOWNLINE PRESENTLINE FA I LU RESERVICE TESTALPHATEC HN O LO G IE SALARM OFFOUTPUT LOADOVERLOAD100 %75 %50 %2

Page 38 - 4.3 External Modem Operation

36LOW BATTERYWARN INGLOW BATTERYSHUTDOWNLINE PRESENTLINE FA I LU RESERVICE TESTALPHATEC HN O LO G IE SALARM OFFOUTPUT LOADOVERLOAD100 %75 %50 %2

Page 39 - 5.1 Remote RS-232 Operation

35LOW BATTERYWARN INGLOW BATTERYSHUTDOWNLINE PRESENTLINE FA I LU RESERVICE TESTALPHATEC HN O LO G IE SALARM OFFOUTPUT LOADOVERLOAD100 %75 %50 %2

Page 40

344.3 External Modem Operation, continued4. OPERATIONRemote Access Using External ModemWhen the remote access feature is enabled, the CFR sends the a

Page 41

334.3 External Modem Operation, continued4. OPERATIONSending Automatic Alarms When a power event takes place, the CFR stores it in an event buffer.

Page 42

324.3 External Modem Operation4. OPERATIONInitializing the ModemFor proper operation, the CFR needs to initialize the modem before usingit. Since a

Page 43

314.2 External Modem Configuration, continuedConfiguring the modem to work with CFRThe CFR uses a three wire interface (RX, TX, and GND) to communicat

Page 44

304. OPERATION4.2 External Modem Configuration, continuedEnabling External ModemAll CFRs are shipped with the modem feature disabled. The followingc

Page 45

THE ALPHA CFRiIMPORTANT:EMERGENCY SHUTDOWN PROCEDURE ON INSIDE BACK COVERTable Of ContentsThe Alpha CFR1500 and CFR 1500 RMUninteruptible Power Suppli

Page 46

294.2 External Modem ConfigurationSpecificationsModem: USRobotics Sportster external modem, 1200, 9600, 19.2K, or28.8K baud or any Hayes compatible mo

Page 47

284. OPERATION4.1 Start-up, Test and Shutdown, continuedSwitching OFF the UPS:1. Switch all equipment connected to the UPS OFF.2. Switch the rear pane

Page 48

27Manual Self-testPress (and hold for several seconds) the “MANUAL START” switch, locatedon the Standard Interface Panel, when the UPS is running on A

Page 49

264.1 Start-up, Test and ShutdownNOTE: ALL rack mount units require an external battery pack. Beforeattempting to operate these units without a batte

Page 50

253. INSTALLATION3.4 208 VAC vs 240 VAC (60 Hz) ConfigurationsFig.14208 VAC Output Schematic (for reference only)Fig. 15120/120/240 VAC Power distribu

Page 51

243.4 208 VAC vs 240 VAC (60 Hz) ConfigurationsSince loads are shared, it is possible to exceed the rated maximum outputcurrent of one of the transfor

Page 52

23In North America, there are only two recognized supply voltages: 208VAC (most commonly used in industrial, commercial, and office areas); and 240VA

Page 53

22The CFR is designed so that battery backup time can be greatly extendedsimply by plugging the EBP 48 External Battery Pack to the back of the UPS.Ba

Page 54

213. INSTALLATION3.2.1 Terminal Block Input and Output Wiring, continued* CAUTION: Refer to the nameplate voltage and frequency ratings affixed to the

Page 55

203. INSTALLATION3.2.1 Terminal Block Input and Output Wiring1. Connect a dedicated ground wire from the GROUND lug on the back of the CFRto an electr

Page 56

iiTHE ALPHA CFR4.3 External Modem Operation 32Initializing the ModemSending Automatic AlarmsRemote Access Using External Modem4.4 Using the Standard I

Page 57

193. INSTALLATION3.2 Connecting the CFR (Plug and receptacle)CAUTION: Installation and wiring should be performed by qualified servicepersonnel in ac

Page 58

183. INSTALLATION3.1 Pre-InstallationDo not connect the CFR UPS to a line conditioner, isolation transformer orany other similar type of device. Dama

Page 59

172. FEATURES2.6 RS–232 Communication Options, continuedDesktop IID RS–232 PortThe RS–232 port on the desktop IID can be used for access with a PC ora

Page 60

16Terminal Emulation SetupIf you are using a PC with terminal emulation software (such as PROCOMM)to communicate with the CFR, use the following setup

Page 61

152.6 RS-232 Communication Options2. FEATURESRS–232 ConnectorThe connection/specifications for the RS–232 serial port vary dependingon the installed i

Page 62

14Fig. 8External Alarms Connector Pin-out(with Factory installed EPO Switch Option)2.5 Communication / Interface Options, continued2. FEATURESPin 1N.C

Page 63

13External IID ConnectorThe external IID connector provides an interface for the optional desktopIntelligent Interface Device (IID). This allows the

Page 64

122. FEATURESLAN Interface ConnectorThe Alpha UPS provides a LAN interface port on a DE-9 female connector.This port may be used to monitor the status

Page 65

112. FEATURES2.5 Communication / Interface Options, continuedPin 1 Pin 1RJ-45(External Alarms)MMJ(External IID)Fig. 5CFR-UPS Connector Identification

Page 66

102. FEATURES2.5 Communication / Interface OptionsThe CFR is equipped with four rear panel jacks for communication andremote interfaces: RS-232 Serial

Page 67

11.1 The Alpha CFRCongratulations on your purchase of one of the most advanced andintelligent Controlled Ferroresonant-Uninterruptible Power Supply (C

Page 68

92. FEATURESFig. 4Intelligent Interface Device2.4 Information Management Options, continuedIntelligent Interface Device (optional)The Intelligent Inte

Page 69

8LOW BATTE R YWARN INGLO W BATTER YSHUTDOWNLINE PRESENTLINE FAILURESE R VICETESTALPHATECHNOLOGIESALARM OFFOUTPUT LOADOVERLOAD100 %75 %50 %25 %MAN

Page 70

7Fig. 2aCFR 1500RM Rear Panel2. FEATURESFig. 2bCFR 1500 Rear Panel2.3 CFR Rear Panel10. Exhaust FanThe CFR1500 contains a rear panel exhaust fan to e

Page 71

62. FEATURES2.3 CFR Rear Panel1. AC Line CordThe UPS is equipped with a standard, grounded AC line cord.2. EXTERNAL BATTERY ConnectorThe connector ac

Page 72

52. FEATURES2.1 A Tour of the CFRThe Alpha CFR is designed to be easy to use and extremely flexible. TheCFR’s interchangeable front panel interface d

Page 73

41.3 Unpacking and InspectionCarefully remove the UPS from its shipping container. Inspect the contents.If items appear to be damaged or missing, con

Page 74

31.2 The CFR Advantage, continuedCOMMUNICATIONS AND INTELLIGENCE Alpha's interchangeable Standard Interface Device and Intelligent InterfaceDevic

Page 75

21.2 The CFR AdvantageADVANCED POWER PROTECTION TECHNOLOGYPower protection devices can be judged by the type and quality of powerthey provide. Alpha

Page 76 - , continued

11.1 The Alpha CFRCongratulations on your purchase of one of the most advanced andintelligent Controlled Ferroresonant-Uninterruptible Power Supply (C

Page 77

iiTHE ALPHA CFR4.3 External Modem Operation 32Initializing the ModemSending Automatic AlarmsRemote Access Using External Modem4.4 Using the Standard I

Page 78

21.2 The CFR AdvantageADVANCED POWER PROTECTION TECHNOLOGYPower protection devices can be judged by the type and quality of powerthey provide. Alpha

Page 79

THE ALPHA CFRiIMPORTANT:EMERGENCY SHUTDOWN PROCEDURE ON INSIDE BACK COVERTable Of ContentsThe Alpha CFR1500 and CFR 1500 RMUninteruptible Power Suppli

Page 80

THE ALPHA CFRIMPORTANT SAFETY PRECAUTIONSCarefully unpack the unit. Report any shipping damage immediately.Please read the operators manual. If you

Page 81

1. Switch BatteryBreaker OFF2. Remove AC linepower cordEMERGENCY SHUTDOWNIMPORTANTThe CFR UPS contains more than one live circuit. During an emergenc

Page 82 - EMERGENCY SHUTDOWN

F R O M A L P H A T E C H N O L O G I E SOperator’s ManualU N I N T E R R U P T I B L E P O W E R S U P P L I E SAlpha CFR 1500 andCFR 150

Page 83

31.2 The CFR Advantage, continuedCOMMUNICATIONS AND INTELLIGENCE Alpha's interchangeable Standard Interface Device and Intelligent InterfaceDevic