9.  Specifications
Table U Mechanical Specications
Parameter Value
Dimen sion s H x W x D
 mm (in) 
FXM 1100-2000: 5.22 x 15.5 x 8.75 (133 x 394 x 222)
FXM 650: 3.47 x 17 x 9 (89 x 432 x 229)
Weight with out b atteries kg (lb)
FXM 650: 25 (11.3)
FXM 1100-2000: 35 (15.9)
Color
Black
Mou nting
Shelf, rack or wall; horizontal or vertical mount.
Humidity
Operating (non-condensing): Up to 95%
Storage: Up to 95%
Cooling
Method of cooling: forced convection (fan cooled)
Maximum heat release: see table below.
Maximum heat release
Maximum heat release per foot
(meter) of vertical frame height used*
Normal Mode Backup Mode Normal Mode Backup Mode
FXM650-24 9 W 217 W
4.4 W/ft²
(155 W/m²)
105.5 W/ft²
(3723 W/m²)
FXM650-48 9 W 143 W
4.4 W/ft²
(155 W/m²)
69.5 W/ft²
(2452 W/m²)
FXM1100-48 22 W 242 W
7.3 W/ft²
(258 W/m²)
78.4 W/ft²
(2775 W/m²)
FXM2000-48 41 W 439 W
13.2 W/ft²
(469 W/m²)
142.5 W/ft²
(5046 W/m²)
* Based on installation in an equipment rack with 26” overall width and 12” depth,
with 30" maintenance aisle and 24" wiring aisle.
Sound power level
LWAd = 59 dBA with fan at maximum speed.
Mou nting
Shelf, rack or wall; horizontal or vertical mount.
Temperatu re Range
,1, 2
, °C
FXM 650
FXM 1100/2000
Operating: -40 to 55
Storage: -40 to 75
Operating: -40 to 50
3
for 120 VAC unit, -40 to 50 for 230 VAC unit
Storage: -40 to 75
Altitude, m (ft)
Operating
Storage
Operating: Up to 3700
4
(12,000)
Storage: Up to 4600 (15,000)
AC input and outpu t conne ctors
Terminal block, Weco p/n 324-HDS/03 or equivalent (max 10 AWG)
Dry contact connectors
Terminal block, mating plug JITE p/n PTB750B-03-1-03-3 or equivalent (max 16
AWG)
RS-232 connector
DE-9 Female
Ethernet connector
Optional, factory installed RJ-45
Dry contacts
6 sets of single-pole, double-throw relays located on the front panel. They are rated
at 250 VAC, 1A. The factory default settings are:
C1: On Battery.
C2, C3
5
: Low Battery.
C4: Load Shed Timer1.
C5: Alarm.
C6: 48/24 VDC for an external fan. It can be factory congured as a dry contact.