6.5  Making Measurements
The System Status menu lets you make measurements of various Alpha FXM inputs, outputs, temperatures and
other values. You can also use the Alpha UPS Monitor to make these measurements. See “Alpha UPS Monitor”.
6.5.1  Procedure
1. From the Logo screen go to the System Status menu.
2. Press the SELECT button to enter the submenu (Table E).
3. Press the SCROLL button to move between items in the submenu. When you reach the item you want
to measure, stop pressing the button. The measurement is automatically displayed on the LCD. It is
automatically updated every 0.5 second.
Table E System Status Menu
LCD display Meaning Description
VIN Input Voltage The line input voltage into the Alpha FXM.
VOUT Output Voltage The Alpha FXM’s output voltage (true RMS).
IOUT AC
Output Current
(AC)
The Alpha FXM’s AC output current (true RMS).
BATT TEMP
Battery
Temperature
The battery’s temperature (°C).
FREQ IN Input Frequency The frequency of line power into the Alpha FXM (Hz).
OUTPUT PWR Output Power The Alpha FXM’s output power in VA (true RMS).
BATT VOLT Battery Voltage The battery’s output voltage (VDC).
CHGR CUR Charger Current The Alpha FXM’s battery charging current is set to this value (Amps).
SHED TIMER1
Amount of
time until the
dry contact is
activated.
The factory default dry contact for this setting is contact C4. SHED TIMER2 and
SHED TIMER3 can be eld programmed. See “Setting the Timer Contact”. This
display shows the amount of time left in seconds until the contact is activated.
The factory default setting is 2 hours, but this can be changed as shown in
"Programming the Dry Contacts and the Clock".
SHED TIMER2
SHED TIMER3
MAC Address CXC MAC The CXC MAC address will be displayed.
IP Address CXC IP The CXC IP will be displayed.
kWh kW Meter The accumulated output power will be displayed.
Remain Tm
Remaining
Battery Runtime
The remaining runtime of the battery will be displayed.
Serial Number
Unit Serial
Number
The unit serial number of the Alpha FXM will be displayed.