Alpha Technologies FXM2000 Specifications Page 11

  • Download
  • Add to my manuals
  • Print
  • Page
    / 32
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 10
9
UPS Control Modules
Rugged UPS Module
FXM 2000
Consult your Alpha representative for P/N configurations
Electrical
>120Vac Model
Battery string voltage: .......48Vdc
Nominal voltage: ...............120Vac
Nominal frequency: ...........Auto-sensing
Input:
Current: ........................... 17.9A nominal
Voltage: ..........................85 to 175Vac
Output:
Voltage regulation: .........+/- 10% over input voltage range
Power at 50°C:................2000W/VA
>230Vac Model
Battery string voltage: .......48Vdc
Nominal voltage: ...............230Vac
Nominal frequency: ...........Auto-sensing
Input:
Current: ........................... 9.4A nominal
Voltage range: ................150 to 328Vac
Output:
Voltage regulation ..........+/- 10% over input voltage range
Power at 50°C:................2000W/VA
Mechanical
Dimensions:
mm: ................................. 133H x 394W x 222D
inches: ............................5.22H x 15.5W x 8.75D
Weight: ..............................16kg (35lbs)
Environmental
Operating temp range*: .....-40 to 74°C (-40 to 165°F)
Audible noise @ 25°C: ......45dBa @ 1 meter (39in)
*120Vac module derates after 50°C. 230Vac module derates after 55°C
Performance
Typical output voltage THD: ........ <3%
Typical efficiency: ...................... >98% (resistive load)
Typical transfer time: ................. <5ms
MTBF:
@ 0.0°C: .......................... 246,206 hrs
@ 25.0°C: ........................174, 955 hrs
@ 50.0°C: ........................103,030 hrs
Power Connector Options
Agency Compliance
Electrical safety: ................UL1778, CSA 22.2 No 107.3-03
Marks:
EMI: ...................................Class A FCC/CISPR
[EN 50091-2:1995]
*Ethernet SNMP card is standard on the 120Vac model and optional on the 230Vac model
**CE applies to 230Vac version only
> 2000W/VA UPS module designed to operate in extreme environments and provide maximum flexibility while ensuring
critical loads remain protected and running during power outages and other power disturbances
> Wide range Automatic Voltage Regulation (AVR) lengthens battery life by providing protection without transferring to
backup mode during voltage surge or sag
> Independently programmable control and report dry contacts allow monitoring and controlling of key functions
> Temperature compensated battery charging protects batteries from overcharging or undercharging at extreme
temperatures, extending the life of the battery
> Local and remote monitoring and control via RS232 port and Ethernet SNMP interface*
> UPS panels can be rotated, improving usability and viewing convenience
120Vac Model
Input Output
Standard
Terminal
Block
Terminal
Block
Optional
Terminal
Block
Terminal Block
+ Dual 5-15R
230Vac Model
Standard
Terminal
Block
Terminal
Block
**
Page view 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16 ... 31 32